  gb60s 60w single output general purp ose www.slpower.com gb60s 18-dec-14 1 features  2? x 3? x 1.0? package  for 1u applications  60w convection cooled  universal input 90-264vac  optional power on led  approved to csa/en/iec/ul60950-1, 2 nd edition  level v efficiency compliant models  less than 0.5w no-load power consumption  3 year warranty  rohs compliant description the gb60s series models provide a highly reliable p ower source in high density 2? x 3? x 1.0? package. fully compliant to the applicable safety and emc st andards, these models will allow easy integration i nto many industrial and ite applications. all 4 models are ce marked to low voltage directive and approved to ite standards of en60950, 2 nd edition. model selection model output current output power ripple & total ovp number * volts convection cooled convection cooled noise* * regulation threshold gb60s12k 12v 4.58a 55w 120mv pk-pk 2% 14.4-18vdc gb60s15k 15v 4.00a 60w 150mv pk-pk 2% 18-22.5vdc GB60S24K 24v 2.50a 60w 240mv pk-pk 2% 28.8-36vdc gb60s36k 36v 1.67a 60w 360mv pk-pk 2% 43.2-54vdc gb60s48k 48v 1.25a 60w 480mv pk-pk 2% 57.6-72vdc notes: * models with 24v or higher output voltage meet efficiency requirements of level v ** measured with noise probe directly across output terminals, and load terminated with 0.1 f ceramic and 10 f low esr capacitors. at -20c, the noise and ripple is 2% of the output. general specifications ac input 100-240vac, 47-63hz, 1 ? rated 80?270vac, 47-440hz operational turn on time 2 sec. max. @120vac input current 120vac: 1.4a, 240vac: 0.75a hold-up time 16ms min. @ 60w load, 120vac input inrush current 240vac, cold start: will not exceed 40a signals optional power on led input fuses 4a, 250vac fuse provided on all models overload protection hiccup mode, 120% to 180%, typical
gb60s 60w single output general purp ose www.slpower.com gb60s 18-dec-14 2 general specifications (continued) earth leakage current <1ma@240vac, nc short circuit protection hiccup mode power factor not applicable overtemperature protection self-recovering efficiency 88% typical (83% for 12v& 85% for 15v) safety standards csa/en/iec/ul60950-1, 2 nd edition. see below for detailed standards information. output power 60w continuous (55w for 12v models) isolation input-output: 4000vac input-ground: 1800vac output-ground: 500vac peak output power not applicable operating temperature -40c start up. -20c to 80c with derating specified in fig.1 ripple and noise see chart above output power derating see fig.1 on page 4 output voltage see chart storage temperature -40c to +85c voltage adjustability fixed relative humidity 5% to 95%, non-condensing minimum load not required altitude operating: 3000 meters non-operating: 40,000 ft. total regulation +/- 2%. see chart mtbf over 600,000 hours per telcordia transient response 500s max. to 1%, 50% load step. 0.2a/s, 3.5% deviation typical vibration random vibration per mil-std-810e, method 514.4, cat. 1, figure 514.4.1, 1 hour in each of 3 axes. switching frequency 65khz, typical shock half-sine, 40 gpk, 10 ms duration, +/- in each of 3 axes, 6 shocks total dimensions 2.0? x 3.0? x 1.0? 50.8 x 76.2 x 25.4mm weight 126g notes: 1. specifications subject to change without notice. 2. all dimensions in inches (mm), tolerance is .02 ?. 3. mounting holes should be connected together for emi purpose 4. fg is safety ground connection 5. specifications are for convection rating at fact ory settings with 115vac input and 25c ambient unl ess otherwise stated. 6. this power supply requires mounting on metal sta ndoffs 0.20? (5mm) in height.
gb60s 60w single output general purp ose www.slpower.com gb60s 18-dec-14 3 emi/emc compliance conducted emissions en55011/22 class b, fcc part 15 class b radiated emissions en55011/22 class a, fcc part 15 class a with 6db ma rgin static discharge immunity en61000-4-2, 6kv contact discharge, 8kv air dischar ge radiated rf immunity en61000-4-3, 3v/m eft/burst immunity en61000-4-4, 2kv/5khz line surge immunity en61000-4-5, 1kv differential, 2kv common-mode conducted rf immunity en61000-4-6, 3vrms power frequency magnetic field immunity en61000-4-8, 3a/m voltage dip immunity en61000-4-11 100vac, 95% dip/0.5 cycle (criteria a) , 60%/5cycles (criteria b), 30%/25 cycles (criteria a). line harmonic emissions en61000-3-2 class a flicker test en61000-3-3, complies (dmax<6%) mechanical drawing connector information input connector j100 dc output connector j2 ground pin 1) ac line pin 2) empty pin 3) ac neutral pin 1) +vout pin 3) -vout pin 2) +vout pin 4) -vout 19-30258-0187 (keystone 1285)(zierick 895)(.187*0.020) mating connector: tyco/amp 640250- 3 pins = 770461-1 mating connector: amp 640250-4 pins = 770461-1 molex 01-90020005
gb60s 60w single output general purp ose www.slpower.com gb60s 18-dec-14 4 70.0% 80.0% 90.0% 100.0% 6 15 30 45 60 efficiency (%) output power (w) efficiency vs. output power 120vac 240vac characteristic curves output vs. temperature -40c start up. at -20c, the supply meet its full sp ec except ripple & noise might be increased from 1% to 2% of the output voltage 55w convection cooled, derating output power to 30w at 70 c for outputs 12v and 15v 60w convection cooled, derating output power to 50w at 60 c and 40w at 70 c for output voltages 24v 20w convection cooled at 80c fig.1 efficiency vs. loading fig.2 10 30 50 70 -10 0 10 20 30 40 50 60 70 80 output power(w) temperature ( c) output power vs . temperature convection for 12v model
gb60s 60w single output general purp ose www.slpower.com gb60s 18-dec-14 5 ripple & noise to verify that the output ripple and noise does not exceed the level specified in the product specific ation, measured using a scope probe socket with 0.1uf ceramic and a 10uf electrolytic capacitor con nected in parallel across it, 20mhz bw. 24v out , n o l oad , 90v ac , 60h z 24v out , f ull l oad , 90v ac , 60h z 24v out , n o l oad , 264v ac , 50h z 24v out , f ull l oad , 264v ac , 50h z
gb60s 60w single output general purp ose www.slpower.com gb60s 18-dec-14 6 output transient response 50% load step within the regulation limits of minim um and maximum load, di/dt< 0.2a/ sec. recovery time not specified as there is no lap s in regulation with a 50% load step. maximum voltage deviation is 3.5% 24v out , 120v ac , 25% to 75% l oad s tep 24v out , 240v ac , 25% to 75% l oad s tep output overload characteristic 24v out , 90v ac 24v out , 264v ac short circuit protection supply shall protect itself against short circuit c onditions. no damage will occur if the output is sh orted. 24v out , 90v ac 24v out , 264v ac
gb60s 60w single output general purp ose www.slpower.com gb60s 18-dec-14 7 overvoltage protection ovp firing reduces output voltage to <50% of nomina l in <50ms. see models chart for trip ranges. 24v out , f ull l oad , 90v ac , 60h z 24v out , f ull l oad , 264v ac , 50h z turn on time 24v out , f ull l oad , 90v ac , 60h z 24v out , f ull l oad , 264v ac , 50h z hold up time 24v out , f ull l oad , 120v ac , 60h z data sheet ? 2014 sl power electronics corp. the information and specifications contained herein are believed to be correct at the time of publication. however, sl power accepts no responsibility for consequences arising from reproduction errors o r inaccuracies. specifications are subject to chan ge without notice .


▲Up To Search▲   

 
Price & Availability of GB60S24K

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X